VS1-3371 ExactTemp Service Manual

image
#153768

Helpful Tools

  • 5/8” Socket
  • 1-1/4” Socket
  • Small Flat Head Screwdriver
  • Phillips Head Screwdriver
  • Channel Locks
  • Thermometer
  • Needle Nose Pliers
  • Safety Glasses

Legal/Disclaimer/Safety

CAUTION – TIPS FOR REMOVAL OF OLD FAUCET:
Always turn
 water supply OFF before removing existing faucet or dissassembling the valve. Open faucet handle to relieve water pressure and ensure that complete water shut-off has been accomplished.

FLUSHING
Flush supply lines prior to installation is strongly recommended to prevent malfunction of thermostatic cartridge.

WARNING: Risk of scalding 
Varying the calibration of this thermostatic valve to increase water temperature increases the risk of injury from scalding. The installer is responsible for installing the valve and any recalibration of the water temperature in accordance with the instructions.

CAUTION: Danger of scald injury. Valve can be recalibrated to provide higher temperature water.
This valve has been preset at the factory to provide a range of water tempertures. Any change in settings or water inlet conditions from those used during calibration at the factory may raise the outlet temperature and may cause scalding. The responsibility for the proper installation and any recalibration of this valve lies with the installer.

Valve Specifications

DESCRIPTION

  • Brass construction
  • 3/4” IPS Connections
  • Thermostatic Valve design with integral checkstops

OPERATION

  • Temperature lever operates through a 340 degree arc with maximum cold at full clockwise rotation and maximum hot at full counterclockwise rotation
  • Safety stop preset temperature at 105 degrees F (41 degrees C)
  • Safety stop override allows maximum temperature at 120 degrees F (49 degrees C)
  • Factory established temperature range from 70 degrees F (21 degrees C) to 120 degrees F (49 degrees C)
  • Must be used with at least one 3600 valve.

CARTRIDGE

  • 130156 thermostatic cartridge design with non metallic/nonferrous materials

STANDARDS

  • Third party certified to ASME A112.18.1/CSA B125.1, ASSE 1016 and all applicable requirements referenced therein including

image

Exploded Valve Diagram

image

  1. Check Valve
  2. Stop Body
  3. Stop Stem
  4. Temperature Limit Stop
  5. Cartridge Nut
  6. Handle Adapter Nut
  7. Spring
  8. Stem
  9. Screw

For service kit numbers refer to moen.com

Cartridge Diagram

image

  1. Bottom O-Ring
  2. Middle O-Ring
  3. Top O-Ring
  4. Screens
  5. Pre-Set Temperature Alignment Markings (1050)

Trouble Shooting

Problem Description Cause Fix
No flow or reduced flow Reduced flow or no flow from device Stop stems are closed Turn stop stems counterclockwise
No flow or reduced flow Reduced flow or no flow from device Blocked screens on cartridge Remove cartridge and rinse. See “Cartridge Servicing”.
Outlet water temperature too high Water is hotter than 105oF at safety stops or 120oF in full hot Cartridge is out of calibration Remove cartridge and rinse. See “Cartridge Servicing”.
Outlet water temperature too high Water is hotter than 105oF at safety stops or 120oF in full hot Missing or damaged bottom o-ring Replace cartridge. See “Cartridge Servicing”.
Leak from around the cartridge Continuous leak from behind trim Cartridge has missing or damage top o-ring. Replace cartridge See “Cartridge Servicing”
Leak from around the cartridge Continuous leak from behind trim Missing or loose cartridge nut Replace or tighten cartridge nut. “Cartridge Servicing.
All hot or cold water Temperature adjustment does not provide mixed temperatue Inlets are reversed Reinstall with hot water line to hot side of the valve and cold water line to cold side of the valve
No temperature stop detected Handle rotates greater than 200o and does not engage a stop Temperature limit stop is not properly seated in the valve Reassemble temperature limit stop. See “Cartridge Servicing”.

Cartridge Calibration

Rotate the temperature control counterclockwise from the coolest setting (80o F) at the 7:00 position to the safety stop setting (105o F) at the 12:00 position.

Push in the end of the stem to activate the safety stop override, then rotate the stem counterclockwise from (105o F) at the 12:00 position to the maximum temperature (120o F) at the 9:00 position. (fig.1)

Use a thermometer to test the temperature of the water. If it is 120o For less, turn the water off and attach your trim. No calibration is necessary.

3371_ExactTemp_Service_Manual07.jpg

If the temperature is higher than 120o F, the valve must be calibrated to a lower temperature. To lower the maximum temperature, proceed to step 2 on page 7. Rotate the temperature stem from the hottest position (9:00) clockwise to the safety stop position position (12:00). This is 1/4 of a turn and the stem will pop out when the proper position is reached. 

Continue rotating the stem clockwise from the (12:00) position to the (2:00) position. (fig.2)

image

While holding the stem to prevent rotation, remove the screw turning counterclockwise. Pull the stem from the valve without rotating.(fig.3)

image

Rotate the stem from the (2:00) position counterclockwise to the (12:00) position.(- fig.4)

image

Replace the stem in the new position and secure with screw. (fig.5)

image

test the temperature of the water. If it is still over 120˚ F, repeat steps 3 and 4 to lower the maximum temperature.

Cartridge Servicing

Removal of cartridge:

  1. If water supply shut off valves are not accessible or are not present, actuate the stops by rotating the stop stem clockwise. Do not over tighten stop stem as this could damage the check valve. (fig.1)
  2. While holding the stem to prevent rotation, remove the screw turning counterclockwise. (fig.2)
  3. Remove spring. (fig.3)
  4. Using a wrench, remove the handle adapter nut by turning counterclockwise. (fig.4)
    3371_ExactTemp_Service_Manual12fig1.png3371_ExactTemp_Service_Manual12fig2.png3371_ExactTemp_Service_Manual12fig3.png3371_ExactTemp_Service_Manual12fig4-1.png
  5. Using a 1-1/4” socket, remove the cartridge retaining nut by turning counterclockwise.

    image

  6. Remove temperature limit stop.

    3371_ExactTemp_Service_Manual14-1.jpg

  7. Remove cartridge by using a wrench to pull out the cartridge.
    3371_ExactTemp_Service_Manual15.jpg

Installation of the cartridge:

  1. Verify that the cartridge is properly set by aligning the drilled hole in the cartridge stem to the indent on the cartridge body.
    3371_ExactTemp_Service_Manual16.png
  2. Assemble the temperature limit stop to the cartridge ensuring that the key on the temperature limit stop is aligned to the slot in the cartrige.
    3371_ExactTemp_Service_Manual17.jpg
  3. By pushing on the front of the temperature limit stop, insert cartridge into the valve body until the temperature limit stop key is fully seated into the valve.
    Screen Shot 2019-02-13 at 1.38.49 PM.png Screen Shot 2019-02-13 at 1.38.59 PM.png
  4. Using a 1-1/4” socket, install the cartridge retaining nut in the valve.
    3371_ExactTemp_Service_Manual19.png
  5. Using a wrench, install the handle adapter nut onto the valve.
    3371_ExactTemp_Service_Manual20.jpg
  6. Install spring.
    3371_ExactTemp_Service_Manual21.jpg
  7. Without rotating the cartridge stem, align the temperature limit stop and the stem.
    3371_ExactTemp_Service_Manual22.png
  8. While pushing in the stem, install the screw by turning clockwise until the screw bottoms out.
    3371_ExactTemp_Service_Manual23.jpg
  9. If integrated stops were used, release them by turning stop stem counterclockwise until they stop.
    3371_ExactTemp_Service_Manual24.gif

Replacing Stops & Checks

NOTE: If servicing stops, water shut off valves must be shut off prior to removal. 

Removal of the stops and checks: 

  1. Using a 5/8” socket, remove the stop by turning counterclockwise.
    3371_ExactTemp_Service_Manual25.jpg

  2. Using pliers, remove check valve by pulling on the check valve’s ribs.
    3371_ExactTemp_Service_Manual26.jpg

Installation of the stops and checks:

  1. Push the check valve into the opening.
    3371_ExactTemp_Service_Manual27.jpg

  2. Using a 5/8” socket, install the stop body by turning clockwise.
    3371_ExactTemp_Service_Manual28.jpg

Maintenance Record Thermostatic Mixing Valve

Screen Shot 2019-02-13 at 1.41.14 PM.png

DATE

TECHNICIAN

SERVICE DETAILS

     
     
     
     
     
     

NOTES