Moen Sensor Flush Valve Prior to 2016: 

 

Symptom: The Moen Sensor Flush Valve is continuously running or it will only deliver a trickle of water when the sensor is engaged. 

Solution: There are two Solution options depending if a "clicking" noise is heard when the user moves out of the sensor range. 

Option 1: Click not Detected
  1. Replace the batteries.
  2. Depress the Reset button (A) located near the Dip Switch (B).

Snag_671bb0.png

  1. If a click is not detected after performing the above steps, replace the Solenoid with Service Kit 104435

Snag_698d5c.png

Service Kit 104435

Option 2: Click Detected
  1. Replace the Piston Tip with Service Kit 104537 (10 per package)
  2. Install fresh batteries. 
  3. Depress the Reset button (A) located near the Dip Switch (B).

Snag_67c85c.png

Snag_681a35.png

Service Kit 104537 (10 per package)

 